Instruction manual
–
AQ G3x7 Generator protection IED
205 (211
)
7.2
M
ONITORING FUNCTIONS
Voltage transformer supervision function VTS, (60)
Pick-up voltage inaccuracy
1%
Operation time inaccuracy
<20ms
Reset ratio
0.95
Current transformer supervision function CTS
Pick-up starting inaccuracy at In
<2%
Minimum operation time
70ms
Reset ratio
0.95
Sag and swell (Voltage variation)
Voltage measurement inaccuracy
±1% of Un
Timer inaccuracy
±2% of setting value or
±20ms
7.3
C
ONTROL FUNCTIONS
Synchrocheck function du/df (25)
Rated voltage Un
100/200V, setting
parameter
Voltage effective range
10-110 % of Un
Voltage inaccuracy
±1% of Un
Frequency effective range
47.5
– 52.5 Hz
Frequency inaccuracy
±10mHz
Phase angle inaccuracy
±3 °
Operate time inaccuracy
±3ms
Reset time
<50ms
Reset ratio
0.95