Instruction manual
–
AQ G3x7 Generator protection IED
194 (211
)
6.6
V
OLTAGE MEASUREMENT MODULE
For voltage related functions (over- /under -voltage, directional functions, distance function,
power functions) or disturbance recorder functionality this module is needed. This module
also has capability for frequency measurement.
For capacitive voltage measurement of the synchrocheck reference, the voltage
measurement module can be ordered with reduced burden in channel VT4. In this module
the burden is < 50 mVA.
The main characteristics of the voltage measurement module:
•
Number of channels: 4
•
Rated frequency: 50Hz, 60Hz
•
Selectable rated voltage (Un): 100/
√
3, 100V, 200/
√
3, 200V by parameter
•
Voltage measuring range: 0.05 Un
–
1.2 Un
•
Continuous voltage withstand: 250 V
•
Power consumption of voltage input:
≤
1 VA at 200V (with special CVT module the burden
is < 50 mVA for VT4 channel)
•
Relative accuracy:
±
0,5 %
•
Frequency measurement range:
±
0,01 % at Ux 25 % of rated voltage
•
Measurement of phase angle: 0.5
º
Ux 25 % of rated voltage