Instruction manual
–
AQ G3x7 Generator protection IED
198 (211
)
7
T
ECHNICAL DATA
7.1
P
ROTECTION FUNCTIONS
7.1.1
C
URRENT PROTECTION FUNCTIONS
Three-phase instantaneous overcurrent protection I>>> (50)
Operating characteristic
Instantaneous
Pick-up current inaccuracy
<2%
Reset ratio
0.95
Operate time at 2*In
Peak value calculation
Fourier calculation
<15 ms
<25 ms
Reset time
16
–
25 ms
Transient overreach
Peak value calculation
Fourier calculation
80 %
2 %
Three-phase time overcurrent protection I>, I>> (50/51)
Pick-up current inaccuracy
< 2%
Operation time inaccuracy
±5% or ±
15ms
Reset ratio
0.95
Minimum operating time with IDMT
35ms
Reset time
Approx 35ms
Transient overreach
2 %
Pickup time
25
–
30ms