Table. 5.3.4 - 46. Event codes.
Event Number
Event channel
Event block name
Event Code
Description
2048
32
CUB1
0
Start ON
2049
32
CUB1
1
Start OFF
2050
32
CUB1
2
Trip ON
2051
32
CUB1
3
Trip OFF
2052
32
CUB1
4
Block ON
2053
32
CUB1
5
Block OFF
2112
33
CUB2
0
Start ON
2113
33
CUB2
1
Start OFF
2114
33
CUB2
2
Trip ON
2115
33
CUB2
3
Trip OFF
2116
33
CUB2
4
Block ON
2117
33
CUB2
5
Block OFF
2176
34
CUB3
0
Start ON
2177
34
CUB3
1
Start OFF
2178
34
CUB3
2
Trip ON
2179
34
CUB3
3
Trip OFF
2180
34
CUB3
4
Block ON
2181
34
CUB3
5
Block OFF
2240
35
CUB4
0
Start ON
2241
35
CUB4
1
Start OFF
2242
35
CUB4
2
Trip ON
2243
35
CUB4
3
Trip OFF
2244
35
CUB4
4
Block ON
2245
35
CUB4
5
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.3.4 - 47. Register content.
Date and
time
Event
code
Fault
type
Trigger
current
Fault
current
Pre-fault
current
Fault
currents
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
2048-2245
Descr.
Unbalance
Start
average
current
Trip
-20ms
averages
Start
-200ms
averages
I1, I2, IZ
mag. and
ang.
0
ms...1800s
Setting
group 1...8
active
A
AQ
Q-M210
-M210
Instruction manual
Version: 2.04