Table. 5.3.7 - 65. Event codes.
Event number
Event channel
Event block name
Event code
Description
4224
66
REF1
0
I0d> (87N) Trip ON
4225
66
REF1
1
I0d> (87N) Trip OFF
4226
66
REF1
2
I0d> (87N) Block ON
4227
66
REF1
3
I0d> (87N) Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for ACTIVATED, BLOCKED, etc. The table below
presents the structure of the function's register content.
Table. 5.3.7 - 66. Register content.
Date and time
Event code
Average trigger
currents
Maximum trigger
currents
Residual
currents
Used SG
dd.mm.yyyy
hh:mm:ss.mss
4224-4227
Descr.
Biascurrent trig
Diffcurrent trig
Characteristics diff
trig
Biascurrent max
Diffcurrent max
Characteristics diff
max
I0Calc
I0 meas
Setting group 1...8
active
5.3.8 Motor status monitoring
The motor status monitoring function is designed to be the one place where the user can set up all
necessary motor data and select the used motor protection functions. Settings related to the protection
functions can also be edited inside each function and any changes are updated into this function as
well. In addition to the motor data settings, this function counts the number of times the motor starts,
the number of times the motor start has succeeded, and the number of times the motor has been
stopped. The function also keeps track of the running time and the starting time. Additionally, the
function has a cumulative counter that tells the overall time the motor has been stopped, and it
shows the last time the motor was stopped.
The outputs for the function are the following:
• motor stopped
• motor starting
• motor running
• motor stalled
• missing phase
• load normal
• overloading
• high overcurrent signals.
The signals can be used in indication or in application logics. They are also the basis of the events the
function generates (if so chosen).
The following figure presents a simplified function block diagram of the motor status monitoring
function.
A
AQ
Q-M210
-M210
Instruction manual
Version: 2.04
123