Table. 5.3.5 - 71. Pick-up settings.
Name
Description
Range
Step
Default
I0
set
Pick-up setting
0.005…40.00×I
n
0.001×I
n
1.20×I
n
U0
set
Pick-up setting
1…75%U
n
0.01%U
n
20%U
n
Grounding
type
Network grounding method
1: Unearthed
[32N Var]
2: Petersen coil
GND [32N Watt]
3: Grounded
[67N]
4: I0
Cos
& I0
Sin
broad range with
MCD [32N Var/
Watt]
-
1:
Unearthed
Multi-criteria
detection
Activation of detecting healthy or unhealthy feeder by analyzing
symmetrical components of currents and voltages. Visible when
earthing type is set to I0
Cos
& I0
Sin
broad range mode.
1: Not used
2: Used
-
1: Not
used
Unearthed/
Compensated
border angle
Dividing the angle between unearthed and compensated
tripping (see description later in this document). Visible when
earthing type is set to I0
Cos
& I0
Sin
broad range mode.
-45.0…90°
0.1°
45°
Angle
Tripping area size (earthed network)
±45.0…135.0°
0.1°
±88°
Angle offset
Protection area direction (earthed network)
0.0…360.0°
0.1°
0.0°
Angle blinder
I0 angle blinder (Petersen coil earthed)
-90.0…0.0°
0.1°
-90°
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.