Name
Range
Step
Default
Protection
functions
Description
Max locked
rotor current
0.1…40.0xI
n
0.1xI
n
7.5xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
Maximum locked rotor current of the motor. This
setting defines the current limit which is maximum
current for the motor to draw in locked rotor situation
(starting or stalled). If the measured current exceeds
this setting limit it is considered to be overcurrent fault
and corresponding measures can be applied to
disconnect the feeder and motor from the supply.
Max locked
rotor current A 0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The maximum locked rotor current in amperes.
Max overload
current
0.1…40.0xI
n
0.1xI
n
2.0xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's maximum overload current. Exceeding
this setting stalls the motor. This setting defines when
the thermal replica switches to the short (stall) time
constant. As long as the current stays below this
setting value, the motor should run even when
overloaded.
Max overload
current A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's maximum overload current in amperes.
No load
current <
0.1…40.0xI
n
0.1xI
n
0.2xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Undercurrent
(I<; 37)
The motor's no load current. This setting defines the
“Stopped” condition when the current is below this
setting value. Also, when the current is below this
value, the undercurrent protection stage is locked.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
219