Figure. 5.3.20 - 158. Outputs when motor starting takes too long, with a speed switch.
If the starting condition lasts longer than the safe stall time that has been set, the function trips the
breaker. In this case the motor is either too small to accelerate within the give time frame or there is a
problem with the load eventhough the motor is able to rotate. Letting the starting progress would
endanger the motor.
The function can be set to monitor the situation if the motor stalls after it has started. There are the
signals ("Mechanical jam" and "Motor stalled") available In the motor protection module, and both can
be used to direct the tripping of the motor.
When the Ist> function is in stall detection and monitor mode, it uses the same default settings for the
motor stall than for the starting conditions. The function monitors either given definite time, or the
I
2
t
value and the speed switch input. If given time is exceeded during the stall time the function initiates
tripping of the motor from the stall condition.