Figure. 5.3.25 - 191. Simplified function block diagram of the TM> function.
Measured input
The function block uses analog phase current measurement values. The function block uses TRMS
values from the whole harmonic specter of 32 components.
Table. 5.3.25 - 186. Measurement inputs of the TM> function.
Signal
Description
Time base
IL1TRMS
TRMS measurement of phase L1 (A) current
5ms
IL2TRMS
TRMS measurement of phase L2 (B) current
5ms
IL3TRMS
TRMS measurement of phase L3 (C) current
5ms
I1
Positive sequence current
5ms
I2
Negative sequence current
5ms
RTD
Temperature measurement for the ambient correction
5ms
Setting parameters
Table. 5.3.25 - 187. General settings (not selectable under setting groups)
Name
Range
Step Default
Description
TM>
mode
0:
Disabled
1:
Activated
-
0:
Disabled
The selection of the function is activated or disabled in the configuration. By default
it is not in use.
Temp C
or F deg
0: C
1: F
-
0: C
The selection of whether the temperature values of the thermal image and RTD
compensation are shown in Celsius or in Fahrenheit.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
277