Table. 5.4.11 - 115. Measured magnitude selection settings.
Name
Description
Range
Step Default
Measured
magnitude
Selection of P-P or P-E voltages. Additionally, the U3 or U4 input can be
assigned as the voltage channel to be supervised.
0: P-P
voltages
1: P-E
voltages
2: U3 input
(2LL-U3SS)
3: U4 input
(SS)
-
0: P-P
voltages
The selection of the AI channel in use is made with a setting parameter. In all possible input channel
variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from
START or TRIP event.
Figure. 5.4.11 - 70. Selectable measurement magnitudes with 3LN+U4 VT connection.
Figure. 5.4.11 - 71. Selectable measurement magnitudes with 3LL+U4 VT connection (P-E voltages not available without
residual voltage).
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
142
© Arcteq Relays Ltd
IM00021
Summary of Contents for AQ-M257
Page 1: ...AQ M257 Motor protection IED Instruction manual...
Page 2: ......