Name
Range
Step
Default
Protection
functions
Description
Nominal
starting
current A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's locked rotor current in amperes.
Start detect
current
0.1…40.0xI
n
0.1xI
n
1.5xI
n
- Motor status
monitoring
- Motor start
monitoring
(Ist>; 48)
The motor starting current detection limit. When in
DOL or Star-Delta mode, this setting defines the motor
starting moment when the measured current exceeds
both the no-load current limit and the start detect
current limit within a ten-millisecond period. If the
current increases slower, it is not defined as a motor
start.
Start detect
current A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Motor start
monitoring
(Ist>; 48)
The motor's starting current detection limit in amperes.
Min locked
rotor current
0.1…40.0xI
n
0.1xI
n
3.5xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting
defines the current limit for when this current is
exceeded while the automatic curve selection and the
control only short time constant (stall) are in use.
Min locked
rotor current A 0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting
defines the current limit for when this current is
exceeded while the automatic curve selection and the
control only short time constant (stall) are in use.
Max locked
rotor current
0.1…40.0xI
n
0.1xI
n
7.5xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
Maximum locked rotor current of the motor. This
setting defines the current limit which is maximum
current for the motor to draw in locked rotor situation
(starting or stalled). If the measured current exceeds
this setting limit it is considered to be overcurrent fault
and corresponding measures can be applied to
disconnect the feeder and motor from the supply.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
185