VUB (4)
U1/U2>/<
U1/U2>>/<<
U1/U2>>>/<<<
U1/U2>>>>/<<<<
47/27P/59PN
Sequence voltage protection
X X X
HOC (4)
Ih>
Ih>>
Ih>>>
Ih>>>>
50H/51H/68H
Harmonic overcurrent protection
X X X
CBFP (1)
CBFP
50BF/52BF
Circuit breaker failure protection
X X X
REF (1)
I0d>
87N
Low-impedance or high-impedance restricted earth
fault/ cable end differential protection
X X X
MST
-
-
Motor status monitoring
X X X
DIF (1)
Idb>/Idi>/I0dHV>/I0dLV> 87T/87N/87G
Generator/transformer differential protection
X X X
TOLM (1)
TM>
49M
Machine thermal overload protection
X X X
LCR (1)
Ist>
48/14
Motor start/locked rotor monitoring
X X X
FSP (1)
N>
66
Frequent start protection
X X X
NUC (1)
I<
37
Non-directional undercurrent protection
X X X
MJP (1)
Im>
50M/51M
Mechanical jam protection
X X X
UPF (1)
PF<
55
Power factor protection
X X
RTD (1)
-
-
Resistance temperature detectors
X X X
PQS (4)
P, Q, S>/<
P, Q, S>>/<<
P, Q, S>>>/<<<
P, Q, S>>>>/<<<<
32
Power protection
X X X
UIM (2)
Z<
Z<<
21U
Underimpedance protection
X X
URX (2)
X<
X<<
21X
Under-reactance protection
X X
IAE (1)
I> U<
50/27
Inadvertent energizing protection
X X
OOS (1)
Pslip
78
Pole slip protection
X X
PGS (1)
PGx>/<
99
Programmable stage
X X X
VMEM (1)
-
-
Voltage memory
X X X
ARC (1)
IArc>/I0Arc>
50Arc/
50NArc
Arc fault protection (optional)
X X X
Table. 5.1 - 4. Control functions of AQ-M257.
FFunction
unction
packa
package
ge
Name (
Name (number of
number of
sta
stages)
ges)
IEC
IEC
ANSI
ANSI
Descrip
Description
tion
A
A B
B C
C
SGS
-
-
Setting group selection
X X X
OBJ
-
-
Object control and monitoring
(10 objects available)
X X X
CIN
-
-
Indicator object monitoring
(10 indicators available)
X X X
VJP
Δφ
78
Vector jump
X X
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
18
© Arcteq Relays Ltd
IM00021
Summary of Contents for AQ-M257
Page 1: ...AQ M257 Motor protection IED Instruction manual...
Page 2: ......