Name
Range
Step Default
Protection
functions
Description
Max
overload
current
0.1…40.0xI
n
0.1xI
n
2.0xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
The motor's maximum overload current. Exceeding this
setting stalls the motor. This setting defines when the
thermal replica switches to the short (stall) time constant. As
long as the current stays below this setting value, the motor
should run even when overloaded.
Max
overload
current A
0.1...5000A
0.1A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
The motor's maximum overload current in amperes.
Hot
condition
theta limit
0.0…100.0% 0.1%
70%
- Motor status
monitoring
- Frequent start
protection (N>;
48)
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
-
Mechanical jam
protection
(Im>; 51M)
Setting the motor's thermal limit for hot and cold situations.
When this setting value is not exceed while a locked rotor
situation occurs, the function uses a cold stall curve
adjusted with the actually used thermal capacity. The
function uses a hot stall curve when this setting value is
exceeded. This hot/cold selection also applies
to starts. Please note that using this setting requires that the
Machine thermal overload protection (Tm>) function is
activated and in use.
Safe stall
time cold
0.1…600.0s
0.1s
20.0s
- Motor status
monitoring
- Frequent start
protection (N>;
48)
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48/14)
- Mechanical
jam protection
(Im>; 51M)
The safe stall time when the motor is cold. Unless this value
is specified, it is set to be equal to the hot stall time. Most
probably this leads to overprotection with the cold motor stall
(best case scenario). This setting value is used for the cold
thermal stall curve selection in automatic control. This
parameter is also used in the motor start-up and the number
of starts calculations.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
198
© Arcteq Relays Ltd
IM00021