Name
Range
Step Default Prot.funcs.
Description
Motor In
A
0.1...5
000.0A
0.1A
-
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
-
Undercurrent
(I<; 37)
- Load jam
protection
(Im>; 51M)
The motor's nominal current in amperes.
Nominal
starting
current
0.1…40.0xI
n
0.1xI
n
6.0xI
n
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49 M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's locked rotor current with the nominal voltage. This
setting is used for automatic curve selection and calculation.
Also, the nominal starting capacity calculation is based on this
value.
Nominal
starting
current
A
0.1...5
000.0A
0.1A
-
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's locked rotor current in amperes.
Min
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
3.5xI
n
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting defines
the current limit for when this current is exceeded while the
automatic curve selection and the control only short time
constant (stall) are in use.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
213