Figure. 5.2.1 - 4. Connections (application 1).
Because of the direction of the CTs and because the CTs' P1/S1 side is always wired to the modules's
odd inputs, the "Differential calculation mode" setting has to be set to "Subtract" (
Protection
→
TrafoModule
→
Idx> [87T,87N]
→
Settings). This way the direction of the measured currents are
checked correctly from the relay's perspective.
The following table presents the initial data of the connection as well as the ratings.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
22
© Arcteq Relays Ltd
IM00021