General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.4.25 - 210. General settings of the function.
Name
Range
Step Default
Description
I>U< I.A.E LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
0: On
Set mode of IAE block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
Pick-up
Figure. 5.4.25 - 137. Operating characteristics of inadvertent energizing protection.
The
Voltage limit U< and Current limit I>/< activation setting parameter controls the the pick-up of
the function. Whenever the measured voltage is under the
Voltage limit U< setting value the function is
"Started". If voltage rises over the setting limit the function will wait for the duration set to
Time delay for
releasing start condition before releasing the start condition. When voltage decreases under Voltage
limit U< the function will wait until duration set to Time delay for U< activation has passed. If the
measured current rises over
Current limit I>/< activation parameter while voltage is under the Voltage
limit U< parameter the function will trip. Keep in mind that even if voltage is over the set limit the
function can trip form rising current if start release time delay is still counting down.
Table. 5.4.25 - 211. Pick-up settings.
Name
Range
Step Default
Description
Voltage
limit U<
0.00...99.00
%Un
0.01
%Un
50.00
%Un
Sets the under voltage limit for the function.
Time
delay for
U<
activation
0.000...1800.000
s
0.005
s
5.000 s
When the voltage drops under the
Voltage limit U< setting the function will
wait for the duration of this parameter setting to activate "start" condition.
Current
limit I>/<
0.05...3.00 xIn
0.05
xIn
0.05 xIn If "start" condition is on and each phase current is above this limit the
function will trip.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
262
© Arcteq Relays Ltd
IM00021