Name
Range
Description/values
1: Temp. estimates
- TT> Used k for amb. temp: the ambient correction factor at a givenmoment
- TT> Max. temp. rise all.: the maximum allowed temperature rise
- TT> Temp. rise atm: the calculated temperature rise at a given moment
- TT> Hot spot estimate: the estimated hot spot temperature including the ambient
temperature
- TT> Hot spot max. all.: the maximum allowed temperature for the object
2: Timing status
- TT> Trip delay remaining: the time to reach 100% theta
- TT> Trip time to rel.: the time to reach theta while staying below the trip limit during
cooling
- TT> Alarm 1 time to rel.: the time to reach theta while staying below the Alarm 1 limit
during cooling
- TT> Alarm 2 time to rel.: the time to reach theta while staying below the Alarm 2 limit
during cooling
- TT> Inhibit time to rel.: the time to reach theta while staying below the Inhibit limit during
cooling
Table. 5.4.28 - 234. Counters.
Name
Description / values
Alarm1 inits
The number of times the function has activated the Alarm 1 output
Alarm2 inits
The number of times the function has activated the Alarm 2 output
Restart inhibits
The number of times the function has activated the Restart inhibit output
Trips
The number of times the function has tripped
Trips Blocked
The number of times the function trips has been blocked
Events and registers
The line thermal overload protection function (abbreviated "TOLT" in event block names) generates
events and registers from the status changes in TRIP and BLOCKED signals. The user can select
which event messages are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.28 - 235. Event messages.
Event block name
Event names
TOLT1
Alarm1 ON
TOLT1
Alarm1 OFF
TOLT1
Alarm2 ON
TOLT1
Alarm2 OFF
TOLT1
Inhibit ON
TOLT1
Inhibit OFF
TOLT1
Trip ON
TOLT1
Trip OFF
TOLT1
Block ON
TOLT1
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for TRIP, BLOCKED, etc. signals. The table below
presents the structure of the function's register content.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
281