Table. 5.2.1 - 15. Per-unit residual current measurements.
Name
Unit
Range
Step
Description
Residual
current I0x
("Res.curr.I0x")
× In
0.000…1250.000 0.001
The RMS current measurement (in p.u.) from the residual current
channel I01 or I02.
Calculated I0
× In
0.000…1250.000 0.001
The RMS current measurement (in p.u.) from the calculated I0 current
channel.
Phase current
I0x TRMS
("Res.curr.I0x
TRMS")
× In
0.000…1250.000 0.001
The TRMS current (inc. harmonics up to 31
st
) measurement (in p.u.)
from the residual current channel I01 or I02.
Peak-to-peak
current I0x
("P-P curr.I0x")
× In
0.000…500.000
0.001
The peak-to-peak current measurement (in p.u.) from the residual
current channel I01 or I02.
Table. 5.2.1 - 16. Primary residual current measurements.
Name
Unit
Range
Step
Description
Primary residual
current I01
("Pri.Res.curr.I0x")
A
0.000…1000000.000 0.001 The primary RMS current measurement from the residual current
channel I01 or I02.
Primary calculated
I0
("Pri.calc.I0")
A
0.000…1000000.000 0.001 The primary RMS current measurement from the calculated
current channel I0.
Primary residual
current I0x TRMS
("Res.curr.I01
TRMS Pri")
A
0.000…1000000.000 0.001 The TRMS current (inc. harmonics up to 31
st
) measurement
from the primary residual current channel I01 or I02.
Table. 5.2.1 - 17. Secondary residual current measurements.
Name
Unit
Range
Step
Description
Secondary residual
current I0x
("Sec.Res.curr.I0x")
A
0.000…300.000 0.001 The secondary RMS current measurement from the residual current
channel I01 or I02.
Secondary
calculated I0
("Sec.calc.I0")
A
0.000…300.000 0.001 The secondary RMS current measurement from the calculated
current channel I0.
Secondary residual
current I0x TRMS
("Res.curr.I0x
TRMS Sec")
A
0.000…300.000 0.001 The secondary TRMS current (inc. harmonics up to 31
st
)
measurement from the secondary residual current channel I01 or I02.
Table. 5.2.1 - 18. Residual current phase angle measurements.
Name
Unit
Range
Step
Description
Residual current angle
I0x
("Res.curr.angle I0x")
deg
0.000…360.000 0.001 The residual current angle measurement from the I01 or
I02 current input.
Calculated I0 angle
deg
0.000…360.000 0.001 The calculated residual current angle measurement.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
29