Table. 5.6.1 - 280. Measured inputs of the CTS function.
Signal
Description
Time base
IL1RMS
RMS measurement of phase L1 (A) current
5ms
IL2RMS
RMS measurement of phase L2 (B) current
5ms
IL3RMS
RMS measurement of phase L3 (C) current
5ms
I01RMS
RMS measurement of residual input I01
5ms
I02RMS
RMS measurement of residual input I02
5ms
I1
Phase current's positive sequence component
5ms
I2
Phase current's negative sequence component
5ms
IL1Ang
Angle of phase L1 (A) current
5ms
IL2 Ang
Angle of phase L2 (B) current
5ms
IL3 Ang
Angle of phase L3 (C) current
5ms
I01 Ang
Angle of residual input I01
5ms
I02 Ang
Angle of residual input I02
5ms
The selection of the AI channel in use is made with a setting parameter. In all possible input channel
variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from
START or TRIP event.
General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.6.1 - 281. General settings of the function.
Name
Range Default
Description
CTS LN mode
1: On
2:
Blocked
3: Test
4: Test/
Blocked
5: Off
0: On
Set mode of CTS block.
This parameter is visible only when
Allow setting of individual LN mode is enabled
in
General menu.
I0 input selection
0: Not in
use
1: I01
2: I02
0: Not
in use
Selects the measurement input for the residual current. If the residual current is
measured with a separate CT, the residual current circuit can be monitored with
the CTS function as well. However, this does not apply to summing connections
(Holmgren, etc.). If the phase current CT is summed with I01 or I02, this selection
should be set to "Not in use".
I0 direction
0: Add
1:
Subtract
0: Add
Defines the polarity of residual current channel connection.
Compensate natural
unbalance
0: -
1:
Comp
0: -
When activated while the line is energized, the currently present calculated
residual current is compensated to 0.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
368
© Arcteq Relays Ltd
IM00021