Now, we set the stage as follows:
Parameter
Setting
Current 1
0.80 kA
Operation 1
30 000 operations
Current 2
16.00 kA
Operations 2
100 operations
Enable Alarm 1
1: Enabled
Alarm 1 Set
1000 operations
Enable Alarm 2
1: Enabled
Alarm 2 Set
100 operations
With these settings, Alarm 1 is issued when the cumulative interruption counter for any of the three
phases dips below the set 1000 remaining operations ("Alarm 1 Set"). Similarly, when any of the
counters dips below 100 remaining operations, Alarm 2 is issued.