Signal
Description
Signal
Description
Status
PushButton x
Off
Status of Push Button 1...12 is
OFF
Always True/False
"Always false" is always "0". Always true is
always "1".
Forced SG in
use
Stage forcing in use
OUTx
Output contact statuses
SGx Active
Setting group 1...8 active
GOOSE INx
GOOSE input 1...64
Double
Ethernet LinkA
down
Double ethernet communication
card link A connection is down.
GOOSE INx quality
Quality of GOOSE input 1...64
Double
Ethernet LinkB
down
Double ethernet communication
card link B connection is down.
Logical Input x
Logical input 1...32
MBIO ModA
Ch x Invalid
Channel 1...8 of MBIO Mod A is
invalid
Logical Output x
Logical output 1...64
MBIO ModB
Ch x Invalid
Channel 1...8 of MBIO Mod B is
invalid
NTP sync alarm
If NTP time synchronization is lost, this
signal will be active.
MBIO ModB
Ch x Invalid
Channel 1...8 of MBIO Mod C is
invalid
Ph.Rotating Logic control
0=A-B-C, 1=A-C-B
Phase rotating order at the moment. If
true ("1") the phase order is reversed.
NO
NOTE!
TE!
Digital channels are measured every 5 ms.
Recording settings and triggering
Disturbance recorder can be triggered manually or automatically by using the dedicated triggers. Every
signal listed in "Digital recording channels" can be selected to trigger the recorder.
The device has a maximum limit of 100 for the number of recordings. Even when the recordings are
very small, their number cannot exceed 100. The number of analog and digital channels together with
the sample rate and the time setting affect the recording size. See calculation examples below in the
section titled "Estimating the maximum length of total recording time".
Table. 5.6.6 - 317. Recorder control settings.
Name
Range
Step
Default
Description
Recorder
enabled
0: Enabled
1: Disabled
-
0:
Enabled Enables and disables the disturbance recorder function.
Recorder
status
0: Recorder ready
1: Recording
triggered
2: Recording and
storing
3: Storing
recording
4: Recorder full
5: Wrong config
-
-
Indicates the status of recorder.
Clear
0…2
32
-1
1
-
Clears selected recording. If "1" is inserted, first recording will be
cleared from memory. If "10" is inserted, tenth (10th) recording will be
cleared from memory.
Manual
trigger
0: -
1: Trig
-
0: -
Triggers disturbance recording manually. This parameter will return
back to "-" automatically.
Clear all
records
0: -
1: Clear
-
0: -
Clears all disturbance recordings.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
399