Name
Range
Description
PSx MagnitudeX
See table below.
Defines the measurement used by the stage. Available parameters
depend on selected measurement type.
PSx MagnitudeX multiplier
-5 000 000...5
000 000
Multiplies the selected measurement. 1 by default (no multiplication).
See section "Magnitude multiplier" for more information.
Analog values
The numerous analog signals have been divided into categories to help the user find the desired value.
Table. 5.7 - 327. Phase and residual current measurements (IL1, IL2, IL3, Io1 and Io2)
Name
Description
ILx ff (p.u.)
Fundamental frequency RMS value (in p.u.)
ILx 2
nd
h.
ILx 2
nd
harmonic value (in p.u.)
ILx 3
rd
h.
ILx 3
nd
harmonic value (in p.u.)
ILx 4
th
h.
ILx 4
nd
harmonic value (in p.u.)
ILx 5
th
h.
ILx 5
nd
harmonic value (in p.u.)
ILx 7
th
h.
ILx 7
nd
harmonic value (in p.u.)
ILx 9
th
h.
ILx 9
nd
harmonic value (in p.u.)
ILx 11
th
h.
ILx 11
nd
harmonic value (in p.u.)
ILx 13
th
h.
ILx 13
nd
harmonic value (in p.u.)
ILx 15
th
h.
ILx 15
nd
harmonic value (in p.u.)
ILx 17
th
h.
ILx 17
nd
harmonic value (in p.u.)
ILx 19
th
h.
ILx 19
nd
harmonic value (in p.u.)
ILx TRMS
ILx TRMS value (in p.u.)
ILx Ang
ILx Angle (degrees)
Table. 5.7 - 328. Other current measurements
Name
Description
I0Z Mag
Zero sequence current value (in p.u.)
I0CALC Mag
Calculated I0 value (in p.u.)
I1 Mag
Positive sequence current value (in p.u.)
I2 Mag
Negative sequence current value (in p.u.)
I0CALC Ang
Angle of calculated residual current (degrees)
I1 Ang
Angle of positive sequence current (degrees)
I2 Ang
Angle of negative sequence current (degrees)
I01ResP
I01 primary current of a current-resistive component
I01CapP
I01 primary current of a current-capacitive component
I01ResS
I01 secondary current of a current-resistive component
I01CapS
I01 secondary current of a current-capacitive component
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
415