Name
Range
Description
Application
ID
("AppID")
0×0…0×3FFF Defines the application ID that will be matched with the publisher's GOOSE control block.
Configuration
revision
("ConfRev")
1…2
32
-1
Defines the configuration revision that will be matched with the publisher's GOOSE control
block.
Data index
("DataIdx")
0…99
Defines the data index of the value in the matched published frame. It is the status of the
GOOSE input.
NextIdx is
quality
0: No
(Default)
1: Yes
Selects whether or not the next received input is the quality bit of the GOOSE input.
Data type
0: Boolean
(Default)
1: Integer
2: Unsigned
3: Floating
point
Selects the data type of the GOOSE input.
Control block
reference
-
GOOSE subscriber can be set to check the GCB reference of the published GOOSE frame.
This setting is automatically filled when Ed2 GOOSE configuration is done by importing cid file
of the publisher.
GOOSE input descriptions
GOOSE inputs can be given a description. The user defined description are displayed in most of the
menus (logic editor, matrix, block settings etc.).
Table. 6.1.6 - 353. GOOSE input user description.
Name
Range
Default
Description
User editable
description GI x
1...31
characters
GOOSE
IN x
Description of the GOOSE input. This description is used in several menu
types for easier identification.
GOOSE events
GOOSE signals generate events status changes. The user can select which event messages are
stored in the main event buffer: ON, OFF, or both. The events triggered by the function are recorded
with a time stamp and with process data values. The time stamp resolution is 1 ms.
Table. 6.1.6 - 354. GOOSE event
Event block name
Event name
GOOSE1...GOOSE2
GOOSE IN 1...64 ON/OFF
GOOSE3...GOOSE4
GOOSE IN 1...64 quality Bad/Good
GOOSE5...GOOSE6
GOOSE Subscription status 1...64 Active/Not active
GOOSE7...GOOSE8
GOOSE Processing simulated messages 1...64 True/False
GOOSE9...GOOSE10
GOOSE Subscription needs commissioning 1...64 True/False
Setting the publisher
The configuration of the GOOSE publisher is done using the IEC 61850 tool in AQtivate (
Tools
→
Communication
→
IEC 61850). Refer to AQtivate-200 Instruction manual for more information on how
to set up GOOSE publisher.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
429
Summary of Contents for AQ-M257
Page 1: ...AQ M257 Motor protection IED Instruction manual...
Page 2: ......