Name
Range
Step
Default
Description
Current deadband
0.01…50.00A
0.01A
5A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00A
0.01A
0.2A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband 0.1…5.0deg
0.1deg
1deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000ms
1ms
-
Displays the integration time of the protocol.
6.1.10 SPA
The device can act as a SPA slave. SPA can be selected as the communication protocol for the COM
B port (RS-485 port in the CPU module). When the device includes a serial RS-232 card connector,
the SPA protocol can also be selected as the communication protocol for the COM E and COM F
ports. Please refer to the chapter "Construction and installation" in the device manual to see the
connections for these modules.
The data transfer rate of SPA is 9600 bps, but it can also be set to 19 200 bps or 38 400 bps. As a
slave the device sends data on demand or by sequenced polling. The available data can be
measurements, circuit breaker states, function starts, function trips, etc. The full SPA signal map can
be found in AQtivate (
Tools
→
SPA map).
The SPA event addresses can be found at
Tools
→
Events and logs
→
Event list.
NO
NOTE!
TE!
To access SPA map and event list, an .aqs configuration file should be downloaded from the
relay.
6.2 Analog fault registers
At
Communication
→
General I/O
→
Analog fault registers the user can set up to twelve (12) channels
to record the measured value when a protection function starts or trips. These values can be read in
two ways: locally from this same menu, or through a communication protocol if one is in use.
The following table presents the setting parameters available for the 12 channels.
Table. 6.2 - 361. Fault register settings.
Name
Range
Step Default
Description
Select
record
source
0: Not in use
1…12: I>, I>>, I>>>, I>>>>
(IL1, IL2, IL3)
13…24: Id>, Id>>, Id>>>,
Id>>>> (IL1, IL2, IL3)
25…28: I0>, I0>>, I0>>>,
I0>>>> (I0)
29…32:
I0d>, I0d>>, I0d>>>, I0d>>>>
(I0)
33: FLX
-
0: Not
in use
Selects the protection function and its stage to be used as the
source for the fault register recording.
The user can choose between non-directional overcurrent,
directional overcurrent, non-directional earth fault, directional
earth fault, and fault locator functions.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
434
© Arcteq Relays Ltd
IM00021