Radiated RF electromagnetic field:
EN 60255-26, IEC 61000-4-3
f = 80…1 000 MHz, 10 V/m
Conducted RF field:
EN 60255-26, IEC 61000-4-6
f = 150 kHz…80 MHz, 10 V (RMS)
Table. 9.3 - 433. Voltage tests.
Dielectric voltage test
EN 60255-27, IEC 60255-5, EN 60255-1
2 kV, 50 Hz, 1 min
Impulse voltage test
EN 60255-27, IEC 60255-5
5 kV, 1.2/50 µs, 0.5 J
Physical environment compatibility
Table. 9.3 - 434. Mechanical tests.
Vibration test
EN 60255-1, EN 60255-27, IEC 60255-21-1
2…13.2 Hz, ± 3.5 mm
13.2…100 Hz, ± 1.0 g
Shock and bump test
EN 60255-1, EN 60255-27, IEC 60255-21-2
20 g, 1 000 bumps/dir.
Table. 9.3 - 435. Environmental tests.
Damp heat (cyclic)
EN 60255-1, IEC 60068-2-30
Operational: +25…+55 °C, 93…97 % (RH), 12+12h
Dry heat
EN 60255-1, IEC 60068-2-2
Storage: +70 °C, 16 h
Operational: +55 °C, 16 h
Cold test
EN 60255-1, IEC 60068-2-1
Storage: –40 °C, 16 h
Operational: –20 °C, 16 h
Table. 9.3 - 436. Environmental conditions.
IP classes
Casing protection class
IP54 (front)
IP21 (rear)
Temperature ranges
Ambient service temperature range
–35…+70 °C
Transport and storage temperature range
–40…+70 °C
Other
Altitude
<2000 m
Overvoltage category
III
Pollution degree
2
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
503
Summary of Contents for AQ-M257
Page 1: ...AQ M257 Motor protection IED Instruction manual...
Page 2: ......