5.4.25 Inadvertend energizing protection (I> U< I.A.E; 50/27)
Inadvertent energizing protection function is intended to be used for protection the generator from
connecting the generator to network when it is not rotating. A machine that is accidentally energized
from the power system can be damaged or completely destroyed.
The power protection function uses a total of eight (8) separate setting groups which can be selected
from one common source.
The function can operate on instant or time-delayed mode.
The operational logic consists of the following:
• input magnitude processing
• threshold comparator
• block signal check
• time delay characteristics
• output processing.
The inputs for the function are the following:
• operating mode selections
• setting parameters
• digital inputs and logic signals
• measured and pre-processed power magnitudes.
The function's outputs are START, TRIP and BLOCKED signals which can be used for direct I/O
controlling and user logic programming. The function generates general time-stamped ON/OFF events
to the common event buffer from each of the three (3) output signals. In the instant operating mode the
function outputs START and TRIP events simultaneously with an equivalent time stamp. The time stamp
resolution is 1 ms. The function also a resettable cumulative counter for the START, TRIP and
BLOCKED events.
Measured input
The function block uses analog current values and positive sequence voltage values calculated from
phase voltages. The monitored magnitudes are equal to RMS values.
Table. 5.4.25 - 209. Measurement inputs of the Z< function.
Signal
Description
Time base
IL1RMS
RMS measurement of phase L1 (A) current
5ms
IL2RMS
RMS measurement of phase L2 (B) current
5ms
IL3RMS
RMS measurement of phase L3 (C) current
5ms
Pos. Seq. Voltage
Positive sequence voltage
5ms
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00021
261