5.4.29 Generator/transformer differential protection (Idb>/Idi>/I0dHV>/I0dLV>; 87T/
87N/87G)
The generator/transformer differential function is used for protecting the following power
transformers: two-winding transformers, and to some extent three-winding and two-winding
transformers that have double outputs and a summing application. This function can also be used for
protecting generators.
Figure. 5.4.29 - 144. Differential protection function can be used for protecting transformers, generators and both at the same
time.