Name
Range
Step
Default
Description
Tracked f
channel C
0.000…75.000Hz 0.001Hz -
Displays the rough value of the tracked frequency in Channel
C.
Alg f fast
0.000…75.000Hz 0.001Hz -
Frequency measurement built from tracked frequencies and
U4 voltage channel samples.
Alg f avg
0.000…75.000Hz 0.001Hz -
Averaged frequency measurement built from tracked
frequencies and U4 voltage channel samples.
System
measured
frequency
0: One f
measured
1: Two f
measured
2: Three f
measured
-
-
Displays the amount of frequencies that are measured.
f.atm.
Protections
0.000…75.000Hz 0.001Hz -
Frequency measurement value used by protection functions.
When frequency is not measurable this value returns to value
set to "System nominal frequency" parameter.
f.atm. Display
0.000…75.000Hz 0.001Hz -
Frequency measurement value used in display. When
frequency is not measurable this value is "0 Hz".
f
measurement
from
0: Not
measurable
1: Avg Ref 1
2: Avg Ref 2
3: Avg Ref 3
4: Track Ref 1
5: Track Ref 2
6: Track Ref 3
7: Fast Ref 1
8: Fast Ref 2
9: Fast Ref 3
-
-
Displays which reference is used for frequency measurement.
SS1.meas.frqs
0.000…75.000Hz 0.001Hz -
Displays frequency used by "system set" channel 1 and 2.
SS2.meas.frqs
SS1f
meas.from
0: Not
measurable
1: Fast Ref U3
2: Fast Ref U4
-
-
Displays which voltage channel frequency reference is used by
"system set" voltage channel.
SS2f
meas.from
0: Not
measurable
1: Fast Ref U4
-
-
Displays if U4 channel frequency reference is measurable or
not when the channel has been set to "system set" mode.
5.3 General menu
The
General menu consists of basic settings and indications of the device. Additionally, the all activated
functions and their status are displayed in the
Protection, Control and Monitor profiles.
Table. 5.3 - 45. Parameters and indications in the
General menu.
Name
Range
Default
Description
Device name
-
Unitname
The file name uses these fields when loading the .aqs configuration file
from the AQ-200 unit.
Device location
-
Unitlocation
Time
synchronization source
0: Internal
1: External
NTP
2: External
Serial
3: IRIG-B
0: Internal
If an external clock time synchronization source is available, the type is
defined with this parameter. In the internal mode there is no external
Timesync source. IRIG-B requires a serial fiber communication option
card.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
52
© Arcteq Relays Ltd
IM00021