Name
Range
Step
Default
Description
S1...S16 module
0: InternalRTD1
1: InternalRTD2
2: ExtModuleA
3: ExtModuleB
4: ExtModuleC
-
0:
InternalRTD1
Selects the measurement module. Internal RTD
modules are option cards installed to the relay.
External modules are Modbus based external
devices.
S1...S16 channel
0: Channel 0
1: Channel 1
3: Channel 2
4: Channel 3
5: Channel 4
6: Channel 5
7: Channel 6
8: Channel 7
-
0: Channel 0 Selects the measurement channel in the selected
module.
S1...S16 Deg C/Dec F
0: Deg C
1: Deg F
-
0: Deg C
Selects the measurement temperature scale (Celsius
or Fahrenheit).
S1...S16 Measurement -
-
-
Displays the measurement value in the selected
temperature scale.
S1...S16 Sensor
0: Ok
1: Invalid
-
-
Displays the measured sensor's data validity. If the
sensor reading has any problems, the sensor data is
set to "Invalid" and the alarms are not activated.
S1...S16 Enable alarm
1
0: Disable
1: Enable
-
0: Disable
Enables/disables the selection of Alarm 1 for the
measurement channel x.
S1...S16 Alarm1 >/<
0: >
1: <
-
0: >
Selects whether the alarm activates when
measurement is above or below the pick-up setting
value.
S1...S16 Alarm1
-101.0…2000.0deg 0.1deg 0.0deg
Sets the pick-up value for Alarm 1. The alarm is
activated if the measurement goes above or below
this setting mode (depends on the selected mode in
"Sx Alarm1 >/<").
S1...S16 sensor
0: Ok
1: Invalid
-
-
Displays the measured sensor's data validity. If the
sensor reading has any problems, the sensor data is
set to "Invalid" and the alarms are not activated.
S1...S16 Enable alarm
2
0: Disable
1: Enable
-
0: Disable
Enables/disables the selection of Alarm 2 for the
measurement channel x.
S1...S16 Alarm2 >/<
0: >
1: <
-
0: >
Selects whether the measurement is above or
below the setting value.
S1...S16 Alarm2
-101.0…2000.0deg 0.1deg 0.0deg
Sets the value for Alarm 2. The alarm is activated if
the measurement goes above or below this setting
mode (depends on the selected mode in "Sx
Alarm2 >/<").
When the RTDs have been set, the values can be read to SCADA (or some other control system). The
alarms can also be used for direct output control as well as in logics.
Events
The resistance temperature detector function (abbreviated "RTD" in event block names) generates
events and registers from the status changes in ALARM and MEAS INVALID. The user can select
which event messages are stored in the main event buffer: ON, OFF, or both. The function offers
sixteen (16) independent stages; the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values. The
function registers its operation into the last twelve (12) time-stamped registers.
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
99
Summary of Contents for AQ-S215
Page 1: ...AQ S215 Bay control IED Instruction manual...
Page 249: ...Figure 7 4 151 Example block scheme A AQ Q S215 S215 Instruction manual Version 2 04 248...
Page 269: ...Figure 8 13 172 Device installation A AQ Q S215 S215 Instruction manual Version 2 04 268...
Page 287: ...10 Ordering information A AQ Q S215 S215 Instruction manual Version 2 04 286...