9.2.2.6 Disturbance recorder
Table. 9.2.2.6 - 181. Technical data for the disturbance recorder function.
Recorded values
Recorder
analog channels
0…20 channels
Freely selectable
Recorder digital
channels
0…95 channels
Freely selectable analog and binary signals
5 ms sample rate (FFT)
Performance
Sample rate
8, 16, 32 or 64 samples/cycle
Recording length
0.000…1800.000 s, setting step 0.001 s
The maximum length is determined by the chosen signals.
Number of recordings
0…100, 60 MB of shared flash memory reserved
The maximum number of recordings according to the chosen signals and operation time setting
combined
9.3 Tests and environmental
Electrical environment compatibility
Table. 9.3 - 182. Disturbance tests.
All tests
CE-approved and tested according to EN 60255-26
Emissions
Conducted emissions:
EN 60255-26 Ch. 5.2, CISPR 22
150 kHz…30 MHz
Radiated emissions:
EN 60255-26 Ch. 5.1, CISPR 11
30…1 000 MHz
Immunity
Electrostatic discharge (ESD):
EN 60255-26, IEC 61000-4-2
Air discharge 15 kV
Contact discharge 8 kV
Electrical fast transients (EFT):
EN 60255-26, IEC 61000-4-4
Power supply input 4 kV, 5/50 ns, 5 kHz
Other inputs and outputs 4 kV, 5/50 ns, 5 kHz
Surge:
EN 60255-26, IEC 61000-4-5
Between wires 2 kV, 1.2/50 µs
Between wire and earth 4 kV, 1.2/50 µs
Radiated RF electromagnetic field:
EN 60255-26, IEC 61000-4-3
f = 80….1 000 MHz, 10 V/m
Conducted RF field:
EN 60255-26, IEC 61000-4-6
f = 150 kHz….80 MHz, 10 V (RMS)
Table. 9.3 - 183. Voltage tests.
Dielectric voltage test
EN 60255-27, IEC 60255-5, EN 60255-1
2 kV (AC), 50 Hz, 1 min
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
283
Summary of Contents for AQ-S215
Page 1: ...AQ S215 Bay control IED Instruction manual...
Page 249: ...Figure 7 4 151 Example block scheme A AQ Q S215 S215 Instruction manual Version 2 04 248...
Page 269: ...Figure 8 13 172 Device installation A AQ Q S215 S215 Instruction manual Version 2 04 268...
Page 287: ...10 Ordering information A AQ Q S215 S215 Instruction manual Version 2 04 286...