After doing this in the logic editor, click
Save and then update logic (Commands
→
Write to relay
→
Logic).
Buzzer activation and deactivation
AQ-S214 and AQ-S254 Alarming IEDs do not have an integrated buzzer. However, if an alarming
buzzer is needed it is possible to connect an external buzzer. I is activated by one of the output relays
of the IED. The user can set up the buzzer control by connecting the ALARM BUZZER signal to an
output (
Control
→
Device I/O
→
Device IO Matrix). Whenever an alarm is activated the ALARM
BUZZER signal will also activate and the output contact can be controlled.
The user can silence the alarm buzzer by pressing the Back
Back button located in the IED panel, or by
connecting a digital input or some other binary signal in the logic to SILENCE ALARM BUZZER.
Clearing latched alarms
Figure. 5.1 - 11. Latched signals as dots.
Latched signals are represented by filled markers in the matrix.
If a latched signals is connected to an alarm, the alarm unit requires the user to push the Back
Back button
in the unit's front panel before the latched signal can be cleared. Using latched signals is generally not
advised in order to keep alarm clearing simple.
Events
The alarm function generates events from the status changes in the monitored signals. The user can
select which event messages are stored in the main event buffer: ON, OFF, or both.
Table. 5.1 - 4. Event messages.
Event block name
Event name
ALARM1
Alarm 1 ON
A
AQ