When calculating the differential current in a basic situation, it is strongly recommended to consider the
following transformer component errors (the illustrated parts in the image below).
Figure. 5.3.10 - 62. Differential current sources (normal operation).
There seven (7) differential current sources for normal operation:
1) Primary side CT measurement accuracy (CTE
pri
)
In this example the primary side CTs are Class 10P, which means the measurement error is 10 %.
2) Secondary side CT measurement accuracy (CTE
sec
)
In this example the secondary side CTs are Class 5P, which means the measurement error is 5 %.
3) Relay measurement accuracy (primary and secondary) (RE
m
)
The relay measurement error is below 0.5 %, its optional accuracy below 0.2 % per measurement
channel: the combined value for both sides is either 1 % or 0.4 %.