Table. 5.2.1 - 19. Per-unit sequence current measurements.
Name
Unit
Range
Step
Description
Positive sequence
current
("Positive sequence
curr.")
× In
0.00…1250.0 0.001
The measurement (in p.u.) from the calculated positive sequence
current.
Negative sequence
current
("Negative sequence
curr.")
× In
0.00…1250.0 0.001
The measurement (in p.u.) from the calculated negative sequence
current.
Zero sequence current
("Zero sequence curr.")
× In
0.00…1250.0 0.001
The measurement (in p.u.) from the calculated zero sequence
current.
Table. 5.2.1 - 20. Primary sequence current measurements.
Name
Unit
Range
Step
Description
Primary positive sequence
current
("Pri.Positive sequence
curr.")
A
0.00…1000000.0 0.001 The primary measurement from the calculated positive
sequence current.
Primary negative sequence
current
("Pri.Negative sequence
curr.")
A
0.00…1000000.0 0.001 The primary measurement from the calculated negative
sequence current.
Primary zero sequence
current
("Pri.Zero sequence curr.")
A
0.00…1000000.0 0.001 The primary measurement from the calculated zero
sequence current.
Table. 5.2.1 - 21. Secondary sequence current measurements.
Name
Unit
Range
Step
Description
Secondary positive
sequence current
("Sec.Positive sequence
curr.")
A
0.000…300.000 0.001 The secondary measurement from the calculated positive
sequence current.
Secondary negative
sequence current
("Sec.Negative sequence
curr.")
A
0.000…300.000 0.001 The secondary measurement from the calculated negative
sequence current.
Secondary zero sequence
current
("Sec.Zero sequence curr.")
A
0.000…300.000 0.001 The secondary measurement from the calculated zero
sequence current.
Table. 5.2.1 - 22. Sequence phase angle measurements.
Name
Unit
Range
Step
Description
Positive sequence current angle
("Positive sequence curr.angle")
deg
0.000…360.0
0.001
The calculated positive sequence current angle.
Negative sequence current angle
("Negative sequence curr.angle")
deg
0.000…360.0
0.001
The calculated negative sequence current angle.
Zero sequence current angle
("Zero sequence curr.angle")
deg
0.000…360.0
0.001
The calculated zero sequence current angle.
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
26
© Arcteq Relays Ltd
IM00028