5 Functions
5.1 Functions included in AQ-T256
The AQ-T256 transformer protection relay includes the following functions as well as the number of
stages in those functions.
Table. 5.1 - 3. Protection functions of AQ-T256.
Name
(number of
stages)
IEC
ANSI
Description
NOC (4)
I>
I>>
I>>>
I>>>>
50/51
Non-directional overcurrent protection
NEF (4)
I0>
I0>>
I0>>>
I0>>>>
50N/51N
Non-directional earth fault protection
CUB (4)
I2>
I2>>
I2>>>
I2>>>>
46/46R/46L
Negative sequence overcurrent/
phase current reversal/
current unbalance protection
HOC (4)
Ih>
Ih>>
Ih>>>
Ih>>>>
50H/51H/68H
Harmonic overcurrent protection
CBFP (1)
CBFP
50BF/52BF
Circuit breaker failure protection
TRF
-
-
Transformer status monitoring
DIF (1)
Idb>/Idi>/I0dHV>/I0dLV> 87T/87N/87G
Transformer differential protection with integrated restricted
earth fault protection
TOLT (1)
TT>
49T
Transformer thermal overload protection
RTD (1)
-
-
Resistance temperature detectors
PGS (1)
PGx>/<
99
Programmable stage
ARC (1)
IArc>/I0Arc>
50Arc/50NArc
Arc fault protection (optional)
Table. 5.1 - 4. Control functions of AQ-T256.
Name
IEC
ANSI
Description
SGS
-
-
Setting group selection
OBJ
-
-
Object control and monitoring
(10 objects available)
CIN
-
-
Indicator object monitoring
(10 objects available)
Table. 5.1 - 5. Monitoring functions of AQ-T256.
Name
IEC
ANSI
Description
CTS (2)
-
-
Current transformer supervision
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00028
15