Table. 6.1.5 - 166. GOOSE input settings.
Name
Range
Step Default
Description
In use
0: No
1: Yes
-
0: No
Enables and disables the GOOSE input in question.
Application ID
("AppID")
0×0…0×3FFF 0×1
0×0
Defines the application ID that will be matched with the publisher's
GOOSE control block.
Configuration
revision
("ConfRev")
1…2
32
-1
1
1
Defines the configuration revision that will be matched with the publisher's
GOOSE control block.
Data index
("DataIdx")
0…99
1
-
Defines the data index of the value in the matched published frame. It is
the status of the GOOSE input.
NextIdx is
quality
0: No
1: Yes
-
0: No
Selects whether or not the next received input is the quality bit of
the GOOSE input.
Data type
0: Boolean
1: Integer
2: Unsigned
3: Floating
point
-
0:
Boolean Selects the data type of the GOOSE input.
GOOSE input descriptions
GOOSE inputs can be given a description. The description will be displayed in several of the menus
(logic editor, matrix, block settings etc.).
Table. 6.1.5 - 167. GOOSE input user description.
Name
Range
Default
Description
User editable
description GI x
1...31
characters
GOOSE
IN x
Description of the GOOSE input. This description is used in several menu
types for easier identification.
Setting the publisher
The configuration of the GOOSE publisher is done using the IEC 61850 tool in AQtivate (
Tools
→
Communication
→
IEC 61850). Refer to AQtivate-200 Instruction manual for more information on how
to set up GOOSE publisher.
6.1.6 IEC 103
IEC 103 is the shortened form of the international standard IEC 60870-5-103. The AQ-200 series units
are able to run as a secondary (slave) station. The IEC 103 protocol can be selected for the serial ports
that are available in the device. A primary (master) station can then communicate with the Arcteq
device and receive information by polling from the slave device. The transfer of disturbance recordings
is not supported.
NO
NOTE
TE: Once the configuration file has been loaded, the IEC 103 map of the relay can be found in the
AQtivate software (
Tools
→
IEC 103 map).
The following table presents the setting parameters for the IEC 103 protocol.
Name
Range
Step
Default
Description
Slave address
1…254
1
1
Defines the IEC 103 slave address for the unit.
Measurement interval
0…60 000ms
1ms
2000ms
Defines the interval for the measurements update.
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00028
247
Summary of Contents for AQ-T256
Page 1: ...AQ T256 Transformer protection IED Instruction manual...
Page 2: ......