Table. 5.4.4 - 98. Synchrocheck stage settings.
Name
Range
Step
Default
Description
SYNx U
conditions
0: LL only
1: LD only
2: DL only
3: LL & LD
4: LL & DL
5: LL & DD
6: LL & LD & DL
7: LL & LD & DD
8: LL & DL & DD
9: Bypass
-
0: LL
only
Determines the allowed states of the supervised systems.
L = Live
D = Dead
SYNx U live >
0.10…100.00%Un 0.01%Un 20%Un
The voltage limit of the live state.
SYNx U dead <
0.00…100.00%Un 0.01%Un 20%Un
The voltage limit of the dead state.
SYNx U diff <
2.00…50.00%Un
0.01%Un 2.00%Un The maximum allowed voltage difference between the
systems.
SYNx angle diff < 3.00…90.00deg
0.01deg
3deg
The maximum allowed angle difference between the
systems.
SYNx freq diff <
0.05…0.50Hz
0.01Hz
0.1Hz
The maximum allowed frequency difference between the
systems.
Events and registers
The synchrocheck function (abbreviated "SYN" in event block names) generates events and registers
from status changes such as SYN OK, BYPASS, and BLOCKED. The user can select which event
messages are stored in the main event buffer: ON, OFF, or both. The function offers three (3)
independent stages; the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.4 - 99. Event codes.
Event number
Event channel
Event block name
Event code
Description
2880
45
SYN1
0
SYN1 Blocked On
2881
45
SYN1
1
SYN1 Blocked OFF
2882
45
SYN1
2
SYN1 Ok ON
2883
45
SYN1
3
SYN1 Ok OFF
2884
45
SYN1
4
SYN1 Bypass ON
2885
45
SYN1
5
SYN1 Bypass OFF
2886
45
SYN1
6
SYN1 Volt condition OK
2887
45
SYN1
7
SYN1 Volt cond not match
2888
45
SYN1
8
SYN1 Volt diff Ok
2889
45
SYN1
9
SYN1 Volt diff out of setting
2890
45
SYN1
10
SYN1 Angle diff Ok
2891
45
SYN1
11
SYN1 Angle diff out of setting
2892
45
SYN1
12
SYN1 Frequency diff Ok
2893
45
SYN1
13
SYN1 Frequency diff out of setting
2894
45
SYN1
14
SYN2 Blocked ON
2895
45
SYN1
15
SYN2 Blocked OFF