• Current
• Residual current
• Voltage
• Residual voltage
• Angle
The range is the same for all of the scaling coefficients. By default, there is no scaling.
• No scaling
• 1/10
• 1/100
• 1/1000
• 1/10 000
• 1/100 000
• 1/1 000 000
• 10
• 100
• 1000
• 10 000
• 100 000
• 1 000 000
Deadband settings.
Table. 6.1.8 - 155. Analog change deadband settings.
Name
Range
Step
Default
Description
General deadband
0.1…10.0%
0.1%
2%
Determines the general data reporting deadband settings.
Active energy deadband
0.1…1000.0kWh 0.1kWh 2kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0kW
0.1kW
2kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0kVA
0.1kVA
2kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00Hz
0.01Hz
0.1Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00A
0.01A
5A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00A
0.01A
0.2A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband 0.1…5.0deg
0.1deg
1deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000ms
1ms
-
Displays the integration time of the protocol.
A
AQ
Q-V211
-V211
Instruction manual
Version: 2.04
244