KNX-IMPZ2 2 Channel Impulse Counter
Page 16
Behaviour on bus voltage recovery
The controller’s outputs start with their current values and the ETS parameter settings are retained.
Delete Program and Reset Sensor
In order to delete the programming ( configuration ) or to reset the module back to delivery status, it must be switched to zero
potential ( disconnect the KNX bus terminal ).
Press and hold the programming button while reconnecting the KNX bus coupler and wait until the programming LED
lights up ( approx. 5-10 seconds ).
Now you can release the programming button.
The module is ready for new configuration now.
If you release the programming button too early, repeat the procedure.