Page 1: ...Installation DXC5K EN IN A22 DXC 5000 INSTALLATION...

Page 2: ......

Page 3: ...CONTENTS 1 SITE SELECTION 5 2 MECHANICAL INSTALLATION 6 3 ELECTRICAL INSTALLATION 7 3 1 Front Views 7 3 2 Connector pin definition and connection 12 4 CONFIGURATION SETTING 30 4 1 Software configurati...

Page 4: ...DXC5K EN IN A22 Installation Page 2 34 DXC 5000 BLANK PAGE...

Page 5: ...Installation DXC5K EN IN A22 DXC 5000 Page 3 34 MODIFICATIONS PAGE Version DATE COMMENTS A 01 10 2004 ORIGINAL ISSUE B 01 03 2005 Add Mini Quad E1 64k G 703 and G SHDSL boards A22 15 05 07 Update...

Page 6: ...ONAL AREA OF NOT LESS THAN 2 5 MM2 ENSURE PROTECTIVE EARTHING CONNECTED BEFORE INSTALL UNINSTALL TELEPHONE WIRES NEVER INSTALL TELEPHONE WIRING DURING A LIGHTNING STORM NEVER INSTALL TELEPHONE JACKS I...

Page 7: ...uideline to select a proper installation site Location of the Rack should be part of the central office equipment layout design Considerations should be given to entrance cable routing and 48 Vdc powe...

Page 8: ...NSTALLATION DXC 5000 and the Y BOX can be installed as a desk top unit or mounted on a 19 inch Mounting of the unit in a rack follows standard telephone rack mount practices Accessories to install on...

Page 9: ...p first after powering on the main unit User can tell which CPU card is primary or redundant from the status of CPU card s ACTIVE led If ACTIVE led is flashing green the CPU card is primary When one C...

Page 10: ...1 7 6 12 5 11 4 10 L12 L11 L10 L9 FXS METERING PLS 12K 16K 600 900 L8 L7 L6 L5 L4 L3 L2 L1 A law U law 3 9 2 8 1 7 6 12 5 11 4 10 L12 L11 L10 L9 FXO E M TEST SIDE A B WIRE 2 4 OHM 600 900 TYPE 1 2 3 4...

Page 11: ...2 12 TIP 1 1 24 channel FXS 24 channel FXO METERING PLS 16K 600 900 METERING PLS 12K 16K 600 900 A law U law 3 9 2 8 1 7 6 12 5 11 4 10 FXO 12K A law U law 3 9 2 8 1 7 6 12 5 11 4 10 FXO RING TIP L E...

Page 12: ...ARDS FOR SINGLE SLOT 3 2 1 H2 H3 H1 V 35 5 5 6 V 35 3 3 4 V 35 1 1 2 V 35 6 V 35 4 V 35 2 A RS232 5 5 RS232 3 3 4 RS232 1 1 2 RS232 4 RS232 2 RS232 X 50 MUX 5 channel RS232 with X 50 subrate 6 channel...

Page 13: ...PANEL VIEWS PLUG IN CARDS FOR DUAL SLOT D0332ENa Y BOX TM B TX LINE TX A TX B RX LINE RX A RX 4 4 B TX LINE TX A TX B RX LINE RX A RX 3 3 B TX LINE TX A TX B RX LINE RX A RX 2 2 B TX LINE TX A TX B R...

Page 14: ...NECTOR The console port is configured as a DCE device with a DB 9 female connector Pin definitions and pin connections are listed in Table 2 4 below Pin Number Signal Source 1 Data Carrier Detect To D...

Page 15: ...1 JUM2 JUM4 JUM3 JUM5 JUM6 JUM1 JUM2 JUM4 JUM3 75 ohm JUM8 JUM8 JUM9 JUM9 JUM10 JUM10 OPEN OFF CLOSE ON FIGURE 10 JUMPER LOCATIONS FOR E1 CARD NOTE 1 For 75 ohm E1 card jumper 9 can be OPEN or ON If t...

Page 16: ...of the U interface ports U PORTs connection to the line is by RJ48C connector The pin definition is listed in Table 2 9 Pin Number Signal 4 TIP 5 RING TABLE 8 U PORT U INTERFACE RJ48C TERMINALS Pin Nu...

Page 17: ...IGNMENT DRY CONTACT I O CARD Pin Number Pin Color Pin Name 8 Brown SG 7 White Brown E 6 Green TIP1 5 White Blue TIP 4 Blue RING 3 White Green RING1 2 Orange M 1 White Orange SB TABLE 12 RJ45 PIN ASSIG...

Page 18: ...B C D Idle on hook 0 0 0 1 0 0 0 0 1 0 ETSI Normal Active off hook 1 1 0 1 1 1 1 1 0 1 1 1 Idle on hook 1 1 0 1 1 1 1 0 1 1 ETSI Revert Active off hook 0 0 0 1 0 0 0 0 0 1 0 0 Idle on hook 0 0 0 0 0 0...

Page 19: ...ENa FIGURE 14 SHORT LINE AND JUMPER SETTING FOR EM CARD SIGNALLING BIT MODE 2 Wire 4 Wire Pin No Pin Name A B Side A Side B Side 4 5 Ring Tip Transmit Receive Transmit Receive 3 6 Ring1 Tip1 Receive T...

Page 20: ...ed 6 Unassigned TABLE 16 RJ11 CONNECTOR PIN ASSIGNMENT FXS FXO CARD FIGURE 15 RJ11 CONNECTOR FXS FXO AND MAG CARDS Ring Generation Ring Detector Pin Number Line Color Description L1 L2 L1 GND 1 White...

Page 21: ...49 TABLE 18 RJ21X CONNECTOR PIN ASSIGNMENT 24 FXS FXO CARD RJ21X PIN t teleco 50 PIN RJ21X PIN t teleco 50PIN LEFT Card Line No L2 T L1 RIGHT Card Line No L2 L1 Line 1 1 26 Line 1 13 38 Line 2 2 27 L...

Page 22: ...S P PLAR OFF PLAR ON FXS FXS P FXS FXS P TX RX TX RX A B C D A B C D A B C D A B C D A B C D A B C D On hook 0 1 0 1 0 1 0 1 0 1 0 1 Off hook 1 1 0 1 1 1 1 1 1 1 0 1 No ring 1 0 1 Ring on 0 0 1 1 1 1...

Page 23: ...ng 0 1 0 1 Ring On 0 0 0 1 Battery Reverse 0 1 0 0 Metering Pulse 0 1 0 0 Tip Lead open 1 1 1 1 Ring lead GND 0 0 0 1 OOS Alarm TABLE 21 SIGNALING BITS DEFAULT SETTING FXO CARD For H W Version F FIGUR...

Page 24: ...nly add Metering Pulse Function JP2 only add Ground Start Function JP2 Jumper setting for Ground Start and Metering Pulse Function For FXS PLAR ABCD bit to fixed 1111 For FXS P or FXS GMP PLAR bit OFF...

Page 25: ...Stop turnning the crank or release the button of the Magneto phone No action TABLE 25 MAGNETO TO MAGNETO SPEAK Status Phone in Local Site Phone in Remote Site Ringing Turn the crank or push and relea...

Page 26: ...Phone to Magneto Phone Status Magneto Phone FXS Phone Ringing Off hook Stop the ring to speak Turn the crank or push and release the button of the Magneto phone End speaking On hook TABLE 28 FXS PLAR...

Page 27: ...2 3 ON 1 2 ON 28 ON 18 ON OFF 19 ON OFF 20 ON OFF 60 OFF ON For Port 3 61 OFF ON 35 2 3 ON 1 2 ON 36 2 3 ON 1 2 ON 38 2 3 ON 1 2 ON 40 2 3 ON 1 2 ON 41 ON 31 ON OFF 32 ON OFF 33 ON OFF 62 OFF ON For P...

Page 28: ...ned 14 Transmit Data Return DTE 15 Transmit Clock DCE 16 Receive Data Return DCE 17 Receive Clock DCE 18 Local Loopback DTE 19 Unassigned 20 Data Terminal Ready DTE 21 Remote Loopback DTE 22 Unassigne...

Page 29: ...back DTE 22 Data Set Ready Return DCE 23 Data Terminal Ready Return DTE 24 External Clock DTE 25 Test Mode DCE TABLE 31 V 36 EIA530 DB25 DTE PORT PIN DEFINITION Pin Number Signal Source 1 Cable Shield...

Page 30: ...ck DCE 16 Unassigned 17 Receive Clock DCE 18 Local Loopback DTE 19 Unassigned 20 Data Terminal Ready DTE 21 Remote Loopback DTE 22 Unassigned 23 Unassigned 24 External Clock DTE 25 Test Mode DCE TABLE...

Page 31: ...NG_Port 1 15 Receive Data RING_Port 1 16 Unassigned 17 Transmit Data RING_Port 2 18 Receive Data RING_Port 2 19 Unassigned 20 Transmit Data RING_Port 3 21 Receive Data RING_Port 3 22 Unassigned 23 Tra...

Page 32: ...ation 4 2 Replacement of Plug in Card When a plug in card is removed and replaced with a card of a different type default configuration is assigned to the new card The user must set the configuration...

Page 33: ...ODE Master CLOCK SOURCE Internal LINE RATE 768k bps LINE CODE 2B1Q DTE V 35 V 36 EIA530 X 21 V 11 Item Default RATE 64K CLOCK Normal DATA Normal RTS Activate TTM Off V 54 Off INTERFACE Depend on which...

Page 34: ...ine Code Mode HDB3 CRC ON RAI ON Alarm Indication Signal FRAMED CAS OFF FDL OFF Sa_bit Sa4 Interface 120 Ohm Hardware Router Setup Default Net_Address 000 000 000 000 Netmask 000 000 000 000 Gateway_A...

Page 35: ...lt Configuration Item Option Range Default A Law A Law Law A Law Impedance 600 ohm 900 ohm 600 ohm Tx Gain 21 to 10 dB 3 dB Rx Gain 21 to 10 dB 3 dB Trunk Condition On hook Off hook On hook Line Polar...

Page 36: ...DXC5K EN IN A22 Installation Page 34 34 DXC 5000 Miscellaneous Default Password DXC5000 Device Name DXC 5000 TABLE 35 DEFAULT SOFTWARE CONFIGURATION...