11
EG
Example n° 1
•
Outdoor unit: G80
•
Number of indoor units: 4 size A (quadri application)
•
Total indoor unit tubing length: 30 meters
•
Emix tank tubing length: 5 meters
•
Total tubing length (including Emix tank): 35 meters
G80 limits in quadri application is 40 meters. The system is ok, without additional load.
Example n° 2
•
Outdoor unit: G80
•
Number of indoor units: 4 size A (quadri application)
•
Total indoor unit tubing length: 50 meters
•
Emix tank tubing length: 7 meters
•
Total tubing length (including Emix tank): 57 meters
G80 limits in quadri application is 65 meters, with additional load. You have to add: 15 g/m x 17 m.
Choose the configuration by the number of indoor units (excluding Emix tank unit) and by the outdoor unit model.
•
Check connection limits including Emix tank unit distance
•
Additional refrigerant charge for Emix tank line ( if needed) is : 15 g/m
Lenght and elevation limits for Emix tank unit are the same as those of standard indoor units.