Emix tank connection-Only DHW application
Emix unit can be used with Iseries outdoor units in a specific configuration in order to create an heat pump system only
for DHW production.
Only DHW application: G30 + Emix tank
Connect Emix tank unit to refrigerant port on the outdoor unit (there is no Emix port) using 1/4 ->3/8 adapter provided
with outdoor unit. The system will operate always in heating mode. Remove JP1 from PCB of Emix tank unit.
Max water temperature: 60° C. It’s not possible to go over 60° C without external energy sources (electric heaters or
similar). However, no errors will be displayed if water temperature set will be over 60° C.
Only DHW application
Connect Emix tank units to standard refrigerant ports on outdoor unit. 1/4->3/8 and 1/2->3/8 adapters are to be field
supplied.
Do not disconnect Emix port bypass; Remove JP1 from every Emix PCBs. The system will operate always in heating
mode; Emix tank units have to be addressed according to refrigerant connection (like multisplit application).
Max water temperature: 60° C. It’s not possible to go over 60° C without external energy sources (electric heaters or
similar). However, no errors will be displayed if water temperature set will be over 60° C.