6. ELECTRICAL DATA
6-1 Electrical characteristics
OUTDOOR UNIT:
AER608SCL
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
Rating conditions
Running Amps.
A
0,110
0,316
2,774
3,200
Power input
kW
0,025
0,069
0,586
0,680
Full load conditions
Running Amps.
A
0,110
0,316
3,074
3,500
Power input
kW
0,025
0,069
0,666
0,760
NOTE: Data referred to indoor unit
AWR608CL
For other indoor unit models there could be some differences.
OUTDOOR UNIT:
AER609SCL
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
Rating conditions
Running Amps.
A
0,120
0,316
3,964
4,400
Power input
kW
0,027
0,069
0,894
0,990
Full load conditions
Running Amps.
A
0,120
0,316
4,464
4,900
Power input
kW
0,027
0,069
1,024
1,120
NOTE: Data referred to indoor unit
AWR609CL
For other indoor unit models there could be some differences.
OUTDOOR UNIT:
AER612SCL
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
Rating conditions
Running Amps.
A
0,130
0,357
5,813
6,300
Power input
kW
0,031
0,078
1,271
1,380
Full load conditions
Running Amps.
A
0,130
0,357
7,013
7,500
Power input
kW
0,031
0,078
1,491
1,600
NOTE: Data referred to indoor unit
AWR612CL
For other indoor unit models there could be some differences.
Rating Conditions:
Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230 V 1-Phase 50 Hz
Outdoor unit
230 V 1-Phase 50 Hz
Outdoor unit
230 V 1-Phase 50 Hz
20