CAN TERMINATED
JUMPER SETTING FOR P1
CAN UNTERMINATED
TB1
TB1 FEEDS RECTIFIER 3
TB2 FEEDS RECTIFIER 2
TB3 FEEDS RECTIFIER 1
( TB1 SHOWN )
TYPICAL AC INPUT TERMINAL BLOCK
L2/N
L1
RIGHT SIDE VIEW
1. GND
2. CAN H
3. NOT CONNECTED
4. CAN L
5. NOT CONNECTED
6. NOT CONNECTED
CAN OUT RJ12 OFFSET
PIN OUT (J3)
P1
J3
SIZE
DWG NO.
TYPE
B
SHEET
TITLE
ISSUE
DATE
OF
TOLERANCES
SCALE
APPROVED
CHECKED
DRAWN
DESIGN
MATERIAL
FINISH
FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.
ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED
THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF
REVISIONS
LTR
DESCRIPTION
APPD
DATE
REV
X.X
0.04"
X.XX
0.02"
X.XXX
0.01"
[X]
1mm
[X.X]
0.5mm
[X.XX] 0.25mm
030-713-08
CUSTOMER CONNECTION
3MDL,CXC,DIN DISTRN, 48-1KW
1 3
DGW
EOF
2004/09
2004/09
D2
c 2004 ARGUS TECHNOLOGIES
O
B
WES
2004/09
NTS
REV BY
B
ADDED LIST 80
S.D.W.
REAR VIEW
(BACK COVER REMOVED)
0.875" KNOCKOUTS
ACCEPT 3/4" CONDUIT
1.125" KNOCKOUTS
ACCEPT 1" CONDUIT
AC INPUT
KNOCKOUT PLATE (REVERSIBLE)
P1
TB1
TB2
TB3
E2 - COMMON (+)
E1 - LIVE ( - )
AC
INPUTS
J3
SIDE ACCESS
DC OUTPUT
LIST 0,9 - 3 MODULES WITH CXC CONTROLLER & DISTRIBUTION
1/4-20 CHASSIS GROUND
USES 1/4-20 HARDWARE
TIGHTEN TO 8FT-LB
Summary of Contents for ALPHA OUTBACK ENERGY Cordex 48-1kW
Page 1: ...Cordex 48 1kW 19 Shelf Flush Mounting Up To 3000W With Distribution 030 713 B2 ...
Page 14: ...This page intentionally left blank ...
Page 38: ...03071305B__ sch 1 Mon May 14 15 17 29 2007 ...