7.0
Adjustments
7.1
Factory Settings / Ranges
7.1.1
48 volt units
Function
Range/ modes
Factory setting
Float Voltage
48-57VDC
52.25VDC
Equalize Voltage
50-60VDC
54.25VDC
Test Voltage
42-62VDC
N/A
HIgh Voltage Shutdown Point
54-61VDC
56.0VDC
Low Voltage Alarm
42-48VDC
44.0VDC
High Voltage Alarm
44-60VDC
55.4VDC
Current Limit (30A unit)
9-33 Amps
31.0 Amps
Current Limit (50A unit)
15-55 Amps
51.0 Amps
Output Slope (30A unit)
0-2%
0.09%
Output Slope (50A unit)
0-2%
0.1%
7.1.2
24 volt units
Function
Range
Factory setting
Float Voltage
24-28.5VDC
26.1VDC
Equalize Voltage
25-30.5VDC
27.1VDC
Test Voltage
21-31VDC
24.0VDC
High Voltage Shutdown Point
27-30VDC
28.0VDC
Low Voltage Alarm
21-24VDC
22.0VDC
High Voltage Alarm
22-30VDC
27.7VDC
Current Limit (50A unit)
15-55 Amps
51 Amps
Current Limit (100A unit)
30-110 Amps
102 Amps
Output Slope (50A unit)
0-2%
0.09%
Output Slope (100A unit)
0-2%
0.1%
7.1.3
Common to 24 volt and 48 volt units
Forced Sharing
enabled/disabled
disabled
Delay Start
0-500 sec
0 seconds
Back light time-out
0-60 minutes
5 minutes
Equalize time-out
1-30 hours
30 hr.
Current limit alarm
enable/disable disable
Remote Access
access/lockout lockout
Remote Adjust
access/lockout lockout
Module ID#
01-99
01
Local access alarm
enable/disable enable
Security code
000-999
123
WARNING: No adjustments should be made to the module while the
input breaker is open or the AC Mains voltage is outside the range
stated in the specifications.
Final adjustments should be done only
when the unit has reached operating temperature. Warm-up of 15 min-
utes is sufficient. :WARNING