7.11.3
Back Light Time-out
The maximum time that the LED back light is active is set in this mode. Although the unit uses long
life LED back lighting the total DC standby current consumption of a unit with no AC connected is
reduced. Using the Up and Down adjustment keys alters the time.
7.11.4
Display Calibration
This control is used to calibrate the modules output voltage display to a known standard DVM read-
ing. Connect the DVM to the modules test jacks (located on the front panel). Using the Up and
Down
adjustment keys change the display until the reading on the module matches the external
meter. Pressing the Enter/Select key sets the calibration of the module. The meter is accurate to
+/- 0.1V (measured at the output of the module just before the output breaker).
7.11.5
(Section Deleted)
7.11.6
Local Access Alarm
When disabled activity of the local control keys will not cause the minor alarm to be activated in the
adjustment, remote communication and test modes. The control toggles between an enabled and
disabled condition. Use the enter/select key to toggle the condition.
7.11.7
Security Code Set
The SECURITY CODE is set to 123 at the factory. To set the security code select the SECURITY
CODE SET
menu item found in the PROTECTED ADJUST submenu. The code is set one digit at
a time by pressing the UP or DOWN keys until the desired number is displayed and the EN-
TER/SELECT
key is pressed. The display will wrap around from 9 to 0 (or 0 to 9) when the Up (or
Down
) key is pressed.