6.0
Adjustments
6.1
Factory Settings/Adjustments
48 Volt units
Float Voltage
48-57VDC
52.3VDC
Equalize Voltage
50-60VDC
54.3VDC
Test Voltage
42-62VDC
——————-
Over Voltage Trip
54-61VDC
56.0VDC
Under Voltage Alarm
42-48 VDC
44.0VDC
Output Slope
0-2%
0%
Current Limit
30-110%
102%
24 Volt units
Float Voltage
24-28.5VDC
26.1VDC
Equalize Voltage
25-30VDC
27.1VDC
Test Voltage
21-31VDC
——————-
Over Voltage Trip
27-30VDC
28.0VDC
Under Voltage Alarm
21-24VDC
22.0VDC
Output Slope
0-2%
0%
Current Limit
30-110%
102%
12 Volt units
Float Voltage
12-15VDC
13.0VDC
Equalize Voltage
13-15VDC
14.0VDC
Test Voltage
10-16VDC
——————-
Over Voltage Trip
13-15VDC
15.0VDC
Under Voltage Alarm
10-12VDC
11.0VDC
Output Slope
0-2%
0%
Current Limit
30-110%
102%
To adjust all settings the use of a small pocket screw driver or tweaker is recommended.
For all controls, to increase a particular level the corresponding adjustment control is rotated clock-
wise. To decrease a level the corresponding adjustment control is rotated counter-clockwise.
6.2
Current Limit
WARNING: Only qualified personnel who are familiar with the configu-
ration and safety requirements of the system to which the unit is at-
tached should perform this operation.
6.2.1
To accurately set the current limit of the rectifier it is necessary to increase the output current of the
unit to greater than the desired current limit point. The possible method of increasing the output are:
Document #010-002-C0 Rev. H Page 16