LINEARIS

Use only cables which are suitable for the diameter of the cable entries.
Cover assembly
During the cover assembly make sure that the cover fi ts correctly.
The cover must not show any damages on the joint surface.
Tighten cover screws evenly (max. 1.2 Nm).

• 

Housing/Cover

No additional bores are allowed in the housing and the cover.

4.5 

Initial operation

4.5.1 

Electrical connection

Hazardous voltage: Possible stroke!
• 

The initial operation must be carried out only by experts!

• 

De-energize the actuator before opening.

• 

Observe the appropriate regulations during electrical installation and initial 
operation.

Connect the actuator as follows:

• 

Connect the ground wire of the electric supply to the appropriate protective earth terminal.

• 

Connect the neutral N to terminal 1.

• 

Follow the steps under „Set up rotation direction“ (S. 10) during connection of the actuator.

• 

Always refer to the wiring diagram located inside the actuator.

Check before you close the circuit for the fi rst time:

• 

Is the actuator undamaged on the outside?

• 

Is the mechanical connection correct?

• 

Has the electrical connection been made regularly?

• 

Check if current type, voltage and frequency match with the motor data (see nameplate on cover and inside the actuator).

• 

Insert suitable cable glands for the connection line.

• 

Observe the wiring diagram inside the cover.

• 

Use separate (shielded) wires for low voltages (e.g. potentiometer).

• 

Set up limit switches prior to initial operation (see page 11).

All elements, such as switches, potentiomer etc., are factory-wired.
Never change the internal wiring.

CAUTION

WARNING

ADVICE

!

Summary of Contents for LINEARIS

Page 1: ...Operating instructions for ARIS Damper Actuator LINEARIS LI1437EN01 Stellantriebe ...

Page 2: ...ing 8 Installation and mounting 8 Initial operation 9 Electrical connection 9 Wiring diagram 10 Operation of the actuators 10 Set up rotation direction 10 Set up limit switches 11 Optional modules and extra features 11 Potentiometer 11 2 wire current output 4 20 mA 12 Gear disengagement 12 Hand wheel option 12 Required customer information 13 Extraordinary situations 13 Troubleshooting and repair ...

Page 3: ...V 50 60 Hz 35VA 1 7 2 mm s 1200N H300 IP65 UT 15 60 C 2ZW GA HR ARIS Stellantriebe GmbH Rotter Viehtrift 9 D 53842 Troisdorf www stellantriebe de Typ Nano S 230V 50 60 Hz 7VA 60 50 s 90 15 Nm UT 15 C 60 C IP54 1ZW Made in Germany Stellantriebe Serial number Actuator type Voltage Frequency Power consumption Actuating time Torque Ambient temperature Protection class Additional built in parts ...

Page 4: ...degree which if not avoided can cause death or heavy injuries CAUTION indicates a hazard with a low risk degree which if not avoided can cause slight or moderate injuries Indicates general advices useful hints and work recommendations which don t have influence on the safety and health of the staff 2 2 General safety advices The actuator components are conform to the state of the art and apply as ...

Page 5: ...ts Near open fires Under water Operating elevators 3 2 Safe and accurate use ARIS actuators are factory checked prior to delivery The final functional testing must be performed within the total system by qualified technical personnel The ARIS company assumes no liability for possible manufacturing errors and resulting damages or subsequent damages after the actuator has been tested installed and d...

Page 6: ...ns 80 125 91 13 65 a 35 13 100 c Hub b 13 6 40 50 16 e 150 7 10 50 Hub 45 x 30 56 38 Hub d 68 X Cover height depending on options 98 178 mm Stroke a b c d e 150 201 341 106 85 278 300 351 491 212 170 428 stroke stroke stroke ...

Page 7: ...rs depending on their utilization and application No longer usable actu ators must not be dismantled as a whole but seperately recycled in parts divided by their materials Non recyclable components must be disposed according to national disposal regulations 4 Actuator setup for use 4 1 Transport and temporary storage Use the factory packaging for transport to the installation point Replace a damag...

Page 8: ...pacitor can effect the rotation stability of the actuators and may cause damages use only ARIS original spare parts Consider prior to attachment of couplings Do not turn the lead screw by force the connection to an actuator or solid underground is made by pre assembled mounting brackets Driver connection 1 The con rods A are connected to the valve by a bolt B 2 Lubricate moving parts OKS 416 or si...

Page 9: ... supply to the appropriate protective earth terminal Connect the neutral N to terminal 1 Follow the steps under Set up rotation direction S 10 during connection of the actuator Always refer to the wiring diagram located inside the actuator Check before you close the circuit for the first time Is the actuator undamaged on the outside Is the mechanical connection correct Has the electrical connectio...

Page 10: ... voltage on terminal 1 and 2 the actuator shaft rotates counter clockwise and results in a pushing stroke Limitation of this stroke with lower switch S1L When the switch is activated line voltage is on terminal 4 2 With line voltage on terminal 1 and 3 the actuator shaft rotates clockwise and results in a pulling stroke Limitation of this stroke with lower switch S2L When the switch is activated l...

Page 11: ...features 5 3 1 Potentiometer Electrical connection Connect terminals 18 19 and 20 according to the desired requirements voltage 50V see page 10 Use only separate shielded wires Adjustment Set up limit switch before adjusting the potentiometer P Approach both end positions electrical ly see chapter 5 2 Observe travel and potentiometer solution Do not overrun the ordered travel to avoid damage to th...

Page 12: ...Gewindespindel gegen selbstständiges Verdrehen gesichert werden 1 Switch off operating voltage of actuator 2 Move lever Auto Manual to position Manual Flow of power between motor and output shaft is interrupted 3 This position serves for quick adjustments of the output shaft during adjustment work 4 Turn the fitting to the desired position no need to disengage output and fittingshafts Control cams...

Page 13: ... situations Run frequent testings during operation Observe especially Intended use of the actuator chapter 3 1 unusual noise heavy vibration or high temperatures check screws for tight seat check cable entries cable glands and blank plugs for tight seat and possible leakness condition of electric wires If failure appear set the actuator out of order and correct the error If you can not correct the...

Page 14: ... head Dismount the drive head only under a load free condition Linear unit Maintenance free by dry run no lubrication necessary We recommend a visible and functional actuator check during plant service work but at least once a year s Kapitel 4 5 1 7 2 Accessories No special tools are required for installation 7 3 Spare parts Order spare parts at aris stellantriebe de any time Please always state t...

Page 15: ...le 2 letter g of the Directive 2006 42 EG The special technical documents according to annex VII part B have been created For reasonable requests these documents can be sent electronically to the responsible authorities Regarding the outgoing electrical hazards of the partly completed machinery the safety objectives of directive 2006 95 EC Low Voltage Directive are complied in accordance with Anne...

Page 16: ...Subject to technical changes ARIS Stellantriebe GmbH Tel 49 2241 25186 0 Rotter Viehtrift 9 Fax 49 2241 25186 99 53842 Troisdorf Germany aris stellantriebe de www stellantriebe de Stellantriebe ...

Reviews: