22
Tensor
2
Set Value
(Contd.)
Performance data for set value input
Resolution: 12 bit
Set value input: Current input 0…20 mA, Burden 50 Ω
Voltage input 0…10 V DC, input impedance >200 kΩ
Actual Value
Settings for actual value output as position feedback, only adjustable with "Signal OUT" = "Ctrl. [mA]" or "Ctrl.
[V]"
Matching the actual value signal for the left and right end position.
This menu item can only be set, when "Ctrl. [mA]" or "Ctrl. [V]" is selected under "Signal OUT".
The actual value signal of both end positions can be set as follows:
Set value signal current = 0mA | 4 mA | 20 mA | free (free values, selectable via display)
Set value signal voltage = 0 V | 2 V | 10 V | free (free values, selectable via display)
For a proper function, the DIP switch near the buttons must be set equivalent to the settings in the menu! Setting the
DIP switch see description for "Signal OUT".
NOTICE: Defaults for the set value of the end positions must cover min. 20% of the total range, otherwise "Error Code
70" will be displayed.
Performance data for actual value output
Resolution: 12 bit
Actual value encoder: Magnetic position sensor
Actual value output: Current input 0…20 mA, Burden 50 Ω
Voltage input 0…10 V DC
Relay Switch
Relay settings for options board with additional switches for position feedback, only adjustable in combination
with mounted relay board
Behaviour setup for the bi-stable relays on the relay board. Up to 4 relays are available, depending on the chosen relay
board.
The switching state of the relays is retained even in currentless condition, so that the auxiliary switches can be used.
Performance data of relay (Add-on board)
Amount of relays: 2 (optional 4)
Relays type: Bi-stable relay
Switching voltage: max. 250 V AC / 125 V DC
Allowed continuous current/channel: max. 2 A (at 230 V AC / 30 V DC); max. 0.2 A (at 125 V DC)
ADVICE
!