23
Tensor
2
Relay Switch
(Contd.)
The following relay settings are available:
1. "Off": Relays switched off/inactive
2. "Sw.pt.high" (Switch point high): Relay is switched on/active from right end position to the set switching point
SP. Relay is switched off/inactive from left end position to the set switching point SP.
3. "Sw.pt.low" (Switch point low): Relay is switched off/inactive from right end position to the set switching point
SP. Relay is switched on/active from left end position to the set switching point SP.
4. "Cam high" (Switch cam high): Relay is switched off/inactive from right end position to the set switching point
SP1, switched on/active between switching points SP1 and SP2 and switched off/inactive again after switching
point SP2. Relay is switched off/inactive from left end position to the set switching point SP2, switched on/
active between switching points SP2 and SP1 and switched off/inactive again after switching point SP1.
5. "Cam low" (Switch cam low): Relay is switched on/active from right end position to the set switching point SP1,
switched off/inactive between switching points SP1 and SP2 and switched on/active again after switching
point SP2. Relay is switched on/active from left end position to the set switching point SP2, switched off/
inactive between switching points SP2 and SP1 and switched on/active again after switching point SP1.
6. "Bl.det.le" (Block detection left): Relay switches off when detecting a blockage in range of the left end position.
Settable only on relays no. 3 & 4!
7. "Bl.det.ri" (Block detection right): Relay switches off when detecting a blockage in range of the right end position.
Settable only on relays no. 3 & 4!
Relay switching state
1 (switched on/active)
0 (switched off/inactive)
left
end position
right
end position
[2] Sw.pt.high
SP
Relay switching state
1 (switched on/active)
0 (switched off/inactive)
left
end position
right
end position
[1] Off