27
Tensor
2
Signal OUT
Output signal
Selection of the output signal type, used as position feedback.
The following position feedbacks are available (depending on activated features):
Feedback signal:
• Off: No feedback of actuator position.
• Ctrl. [mA] (Control [mA], i-Act or current/voltage output): Output of an actual value signal [mA].
• Ctrl. [V] (Control [V], i-Act or current/voltage output): Output of an actual value signal [V].
• Poti (Potentiometer): Output of a voltage value of the internal electrical potentiometer, assigned to the actual
actuator position.
The input signal type must additionally be set up with the onboard DIP switch, according to the desired signal type.
DIP switch 1 and DIP switch 2 must not be active (On) simultaneous!
DIP switch 4 and DIP switch 5 must not be active (On) simultaneous!
Settings of the DIP switch for output signals (DIP switches 4-6)
For the settings of the output signals use DIP switches 4-6.
The position of DIP switches 1-3 is irrelevant to the output signal setting.
i-Act
Current/V
oltage output
Voltage output [V] Current output [mA]
Potentiometer
electronical
Potentiometer output
ADVICE
!
Voltage output
–
+
U
Current output
–
+
I
U
Potentiometer output
Voltage source grounded
5-24V
U-
+
U+
U
U
Potentiometer output
Voltage source potential-free
5-24V
U-
+
U+
U